Dynamic selective harmonic elimination of a three-level inverter used for static VAr compensation

Ran, Li, Holdsworth, Lee and Putrus, Ghanim (2002) Dynamic selective harmonic elimination of a three-level inverter used for static VAr compensation. IEE Proceedings: Generation, Transmission and Distribution, 149 (1). pp. 83-89. ISSN 1350 2360

Full text not available from this repository. (Request a copy)
Official URL: http://dx.doi.org/10.1049/ip-gtd:20020082

Abstract

The paper investigates the harmonic interaction between the AC and DC sides of a 3-level inverter used as a static synchronous VAr compensator (STATCOM). It is illustrated that due to the 3rd harmonic voltage across each DC side capacitor, the conventional selective harmonic elimination modulation (SHEM) may not actually eliminate the target harmonics when the system is on load. A new modulation method, which dynamically adjusts the switching angles according to the operating point, is proposed to overcome this difficulty. The proposed method is verified using simulation and experimental test.

Item Type: Article
Subjects: H600 Electronic and Electrical Engineering
Department: Faculties > Engineering and Environment > Mathematics, Physics and Electrical Engineering
Depositing User: Becky Skoyles
Date Deposited: 12 Feb 2015 16:21
Last Modified: 12 Oct 2019 19:05
URI: http://nrl.northumbria.ac.uk/id/eprint/19367

Actions (login required)

View Item View Item

Downloads

Downloads per month over past year

View more statistics