Zhou, Zhenxin, Chen, Huanxin, Xing, Lu, Li, Guannan and Gou, Wei (2022) An experimental study of the behavior of a model variable refrigerant flow system with common faults. Applied Thermal Engineering, 202. p. 117852. ISSN 1359-4311
|
Text
Revised Manuscript (clean version).pdf - Accepted Version Available under License Creative Commons Attribution Non-commercial No Derivatives 4.0. Download (4MB) | Preview |
Abstract
Variable refrigerant flow (VRF) systems faults are inevitable due to installation errors, degradation, and other reasons. It is of great value to quantitatively understand the impact of faults on VRF systems performance and to clarify the changing trends of variables under different types of faults through experiments. In particular, the experimental analysis of simultaneous faults situations is helpful to improve the fault detection and diagnosis technology of VRF systems. There have been some previous experimental studies on the impact of faults, but none of them concerns modern VRF systems and their simultaneous faults. This paper presents results from a laboratory study of a VRF system with different types of faults. It provides the first published results of combinations of triple simultaneous faults, in addition to previously untested types of double simultaneous faults. The quantitative impact of the three crucial performance parameters, e.g. cooling capacity, system power, and COP, of the system under different faults has been analyzed. In addition, the quantitative influence and variation trend of system parameter variables during single fault and simultaneous fault are summarized. Results show that the outdoor fouling fault has the greatest impact, which can cause a 47.6% COP drop and 80.27% cooling capacity reduction. The influence of the simultaneous fault on the variable trend is superimposed and offset, but the trend influence of some faults also has a dominant characteristic.
Item Type: | Article |
---|---|
Additional Information: | Funding information: The authors gratefully acknowledge the support of National Natural Science of China (Grant number and). |
Uncontrolled Keywords: | Variable refrigerant flow system, Simultaneous faults, Fault impacts, Cooling Capacity |
Subjects: | H200 Civil Engineering H300 Mechanical Engineering |
Department: | Faculties > Engineering and Environment > Mechanical and Construction Engineering |
Depositing User: | Elena Carlaw |
Date Deposited: | 06 Dec 2021 12:14 |
Last Modified: | 26 Nov 2022 08:00 |
URI: | https://nrl.northumbria.ac.uk/id/eprint/47907 |
Downloads
Downloads per month over past year